Twido PLC Modbus Mapping
Apr 28, 2008 12:16 am, by farooq
Subject : PLCs
from the Modbus dept.
Text :
Hi,

My base Twido has got 24 inputs, so I need two word registers to transfer the inputs to read it in SCADA, but am not able to assign the operate block as '%MW100:=%I0.16:23'. Is there any syntax error in this addressing? Twido only takes %i0.0 as the starting address in operate block, even I can't address as '%MW100:=%I0.1:17'.

Can anyone help me in this regard?

Thanks in advance.
Reply


  • Re: Twido PLC Modbus Mapping
    Apr 29, 2008 10:50 pm, by Pascal TONDEUX
    My proposal is the following (tested)

    LD 1
    [%MW100:=%I0.0:16]
    [%MW101:=%I0.16:8]

    Best regards.
    Reply


  • The man who sets out to carry a cat by its tail learns something that will always be useful and which never will grow dim or doubtful. - Mark Twain
    Your use of this site is subject to the terms and conditions set forth under Legal Notices and the Privacy Policy. Please read those terms and conditions carefully. Subject to the rights expressly reserved to others under Legal Notices, the content of this site and the compilation thereof is ©1999-2006 Control Technology Corporation. Powered by Python, Zope, and Squishdot, inspiration by Slashdot. (Vers.ZSQ1.0)