GE Mk VI interface to DCS on Modbus

A

Thread Starter

Anonymous

Can you advise me on possibility/method of connecting a DCS system to GE Mk6 using Modbus serial where the DCS shall be able to do the required DCS control/monitor functions?
 
My Mark V LM connected to Cimplicity HMI, the HMI then connected to serial Honeywell HPM. The serial communication use TCI modbus. The Cimplicity HMI also act as a master for taking some data from HIMA plc, use serial cimplicity.

Hope that help.

Regards,
hmp
 
B

Bob Johnston

Yes you can, if you are familiar with MK V it is not much different, RS232C over Modbus. If you need any more info, give me your Email and I can send you the relevant section of the MK VI Manual.
 
Post your email address and you will receive a copy of GEI-100517, 'MODBUS for HMI Applications.' Should answer just about all your questions. In the meantime, refer to GEI-6126, Chapter 6, the section "MODBUS Data Interface."

markvguy
 
If you want to connect the MK-VI directly, you need a RS232/RS485 converter, then to DCS via RS485.
 
Wouldn't this only be required if the DCS only had an RS-485 port?

And, can you explain "...connect the MK-VI directly,..." Do you mean through the GE Mark VI HMI or directly to a Mk VI processor or serial communications card/port?

markvguy
 
DCS can RS232c communicate with Mk6 control panel processor using a VSCA card . But MK6 seems to be a MASTER,DCS to be a SLAVE.
 
R
DCS means Distributed control system.Its is state of the art technology to control almost any kind of process (chemical)through various controllers.

A set of computers along with a software are interfaced to the real time input outputs from a plant.

This is an integrated solution with various functions are done by periferals over a network
independently.
for more details mail to [email protected]
 
S

S. Chatterjee

Hi, my email address is thisissantanu(at)gmail.com. Could you please send me a copy of GEI-100517,
'MODBUS for HMI Applications'

Thanks in advance for your response.

Regards,
Santanu Chatterjee
 
J
>if you are familiar with MK V it is not much different, RS232C over Modbus... give me your Email and I can send you the relevant section of the MK VI Manual<

please forward relevant section of manual. jasonberry @ solarempowered. com

 
There are two ways to do this. CIMPLICITY has a Modbus Slave, but so does TCI. The TCI Modbus Slave actually gets the Mark VI data from CIMPLICITY using a program called Cimmod, which will run if you select the TCI Modbus option from the CIMPLICITY workbench. This can connect from a seriaal port or over TCP/IP, depending on the configuration in io_ports.dat. TCI Modbus is quite robust, but a little tricky to configure.
 
in my plant, our Foxboro DCS is connected to Mark V using GE GSM protocol.

i'm sure GSM still exist for Mark VI.
 
Hello markvguy
Would you please send me a TCI configuration information, I have a PC crashed and could not use a restore CD to get back the original configuration.
Thanks in advance
 
R
The one of the ways to connect the MKVI HMI with the Foxboro DCS is by the GEGSM protocol. We are using this design in one of our project. which also works well without any problem.
 
N

Nguyen Thanh Son

> Post your email address and you will receive a copy of GEI-100517, 'MODBUS for HMI Applications.' Should answer just about all your questions. In the meantime, refer to GEI-6126, Chapter 6, the section "MODBUS Data Interface."
>
> markvguy <

Please send a copy of GEI-100517 to me!
My Email: [email protected]
Thank you very much.
 
W
Have you considered using OPC? It's way easier. Let me know

Wassim Daoud
Global Solutions Architect
MatrikonOPC
 
P
My company has developed a native communications driver for the GE Mk VI controller. If interested, let me know.

Peter Clout
clout [at] vista-control-com
 
C
Hi Markvguy,

I am looking for these manual very desperately. Can you please send me the manuals at capriconian20[at]yahoo.com. I also need GEI-6126. This will solve my alot of problems.

Thanks
Capriconian
 